The minimum size of service disconnect for a single-family dwelling unit permitted by the NEC is __________ amperes.


A) 60
B) 75
C) 100
D) 150

E) A) and D)
F) B) and C)

Correct Answer

verifed

verified

When testing a "live" 120-volt receptacle using a voltage tester, you should get a 120-volt reading when measuring from the grounded conductor connection (long slot) to the grounding conductor connection (U-shaped slot).

A) True
B) False

Correct Answer

verifed

verified

Which of the following is not a NEC requirement for minimum clearance of a lighting fixture from the storage space in clothes closets?


A) 12" for surface incandescent or LED fixtures
B) 6" for recessed incandescent or LED fixtures
C) 12" for surface fluorescent fixtures
D) 6" for recessed fluorescent fixtures

E) A) and B)
F) None of the above

Correct Answer

verifed

verified

Describe what a circuit tracer does and when it is used.

Correct Answer

verifed

verified

A circuit tracer is used to determine wh...

View Answer

GFCI protection is not required for 125 volt, 15- or 20-ampere receptacles located __________.


A) in bathrooms
B) in finished basements
C) in garages
D) outdoors

E) B) and C)
F) None of the above

Correct Answer

verifed

verified

Type NM cable must be secured no more than ____________________ inches from each single-gang nonmetallic device box.

Correct Answer

verifed

verified

Residential electrical systems may be grounded using only the metal water pipe system and do not need a supplemental grounding electrode.

A) True
B) False

Correct Answer

verifed

verified

A(n) _________________________ is an unintended low-resistance path in an electrical circuit through which some current flows to ground using a pathway other than the intended pathway.

Correct Answer

verifed

verified

When testing a "live" 120-volt receptacle using a voltage tester, you should get a 120-volt reading when measuring from the ungrounded conductor connection (short slot) to the grounding conductor connection (U-shaped slot).

A) True
B) False

Correct Answer

verifed

verified

In the NEC, Article __________ contains requirements for grounding and bonding residential electrical systems.


A) 200
B) 230
C) 240
D) 250

E) None of the above
F) A) and D)

Correct Answer

verifed

verified

In residential applications, Type NM cable is permitted to pass through environmental air handling spaces perpendicular to the long dimension of the space.

A) True
B) False

Correct Answer

verifed

verified

At kitchen countertops, receptacle outlets must be installed so that no point along the wall line is more than __________ feet, measured horizontally, from a receptacle outlet in that space.


A) 2
B) 6
C) 10
D) 12

E) B) and D)
F) B) and C)

Correct Answer

verifed

verified

An electrician tests a 30-ampere, 250-volt dryer receptacle with a voltage tester.The tester indicates 120 volts between the X and Y slots.The tester also indicates 240 volts between the X and W slots.The tester also indicates 0 volts between the Y and the grounding slot.The likely cause is __________.


A) an open grounding path
B) the wires are reversed between the W and the Y slots
C) the wires are reversed between the X and the Y slots
D) an open grounded conductor

E) A) and D)
F) B) and C)

Correct Answer

verifed

verified

When the white grounded circuit conductor is connected to the silver screw on a receptacle and the "hot" ungrounded conductor is connected to the brass screw on the receptacle, you have proper receptacle __________.


A) troubleshooting
B) grounding
C) polarity
D) timing

E) C) and D)
F) None of the above

Correct Answer

verifed

verified

All branch circuits supplying 125-volt, 15- and 20-ampere outlets and devices in residential kitchens, family rooms, living rooms, dining rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms must be protected by a(n) __________


A) fuse
B) circuit breaker
C) GFCI device
D) AFCI device

E) B) and D)
F) A) and D)

Correct Answer

verifed

verified

The minimum length of free conductor at all boxes must be at least __________ inches.


A) 3
B) 6
C) 8
D) 12

E) B) and C)
F) None of the above

Correct Answer

verifed

verified

Receptacle outlets in habitable rooms must be installed so that no point measured horizontally along the floor line in any wall space in more than __________ feet from a receptacle outlet.


A) 2
B) 6
C) 10
D) 12

E) A) and D)
F) None of the above

Correct Answer

verifed

verified

An electrician is testing a circuit where a single-pole switch controls an LED lighting fixture in a bedroom.When the single-pole switch is toggled ON, the lighting fixture does not come on.Which of the following items could not be a cause for this?


A) there is an open grounding path
B) the circuit breaker protecting the circuit is off
C) there are no lamps installed in the lighting fixture
D) the connections to the lighting fixture are not making a good connection

E) B) and D)
F) B) and C)

Correct Answer

verifed

verified

An electrician is testing a 20-ampere, 125-volt duplex receptacle with a voltage tester.The tester indicates 120 volts between the ungrounded slot and the grounded slot.The tester also indicates 0 volts between the ungrounded slot and the grounding slot.The likely cause is __________.


A) an open equipment-grounding path
B) reversed polarity at the receptacle
C) an open grounded circuit conductor
D) a short circuit in the cable feeding the receptacle

E) A) and C)
F) None of the above

Correct Answer

verifed

verified

According to the NEC, all work spaces must be provided with illumination.

A) True
B) False

Correct Answer

verifed

verified